RTA 460MXE Podręcznik Użytkownika Strona 14

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 24
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 13
Real Time Automation, Inc. 12 1-800-249-1612
460 Gateway Device Line 460MXE
BACnet IP Server Settings
1) Scroll down to the BACnet Server row and click Edit. Verify that the Enabled box is checked.
2) Enter the Device Instance that corresponds with your Modbus Slave device/s.
3) In the Device Name field enter a unique name for the device.
4) The Description and Locations fields are optional. Filling in the fields is recommended to identify the
device on a network.
5) Beneath # of Objects to Expose, values should all be kept as zero. These values are dynamically
determined by the runtime of the Modbus slave scan list.
6) Click Save.
7) Click Return to Main Page.
Przeglądanie stron 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 23 24

Komentarze do niniejszej Instrukcji

Brak uwag